Fan type: | Two-stage axial FD Fan |
Name: | FDF-DSA-41-500-1 |
Alternative names: | VDOD-41-500-1; ВДОД-41-500-1 |
Notes: | Stamped blades |
Description
Two-stage axial FD Fans are used for air delivery into combustion chambers of boilers with the capacity of up to 2650 t/h operating with balanced draft (secondary blast). These fans meet the parameters of boiler air path provided the installing two fans of such type for one boiler. All of such fans have left-hand rotational direction. The left-hand rotation is counterclockwise and it should be defined at electric motor side.
We provide a full range of customer service including full warranty, 24/7 consultation and support, valuable insights into the ideal technical solutions in accordance with your requirements and expectations. At your desire we will be glad to supervise or execute the installation and commissioning process. Thanks to strict control over manufacturing process each equipment unit is inspected and recorded so the aftermarket support and spare parts delivery are notable for promptness and full interchangeability. To prolong the life-time of your equipment we are always ready to render on-site services from scheduled maintenance to troubleshooting, equipment inspection and emergency & repair works. All-time we keep our customers informed concerning possible improvements, up-to-date solutions and technical developments which can help to upgrade your equipment and enhance efficiency.
Aerodynamic performance
Capacity: | 1520.0 | ths. m3/h |
Total pressure: | 5511 | Pa |
Temperature: | 100 | C˚ |
Efficiency: | 82,5 | % |
Dustiness: | 0.5 | g/m3 |
Dimensions*
Length (L): | 14800 | mm |
Width (W): | 7320 | mm |
Height (H): | 9100 | mm |
Weight: | 94 000 | kg |
Electric motor
Power: | 3000 | kW |
Rate speed: | 500 | rpm |
Moment of inertia: | н/д | kg*m2 |
* Dimensions can vary depending on electric motor model, customer requirements and design restrictions.
Delivery options
Railway: | Flatcar: 6 Open wagon: 1 Schnabel car: 1 |
This equipment can be searched by the following tags: FDF-DSA-41-500-1, ВДОД-41-500-1, VDOD-41-500-1, Forced draft fan FDF-DSA-41-500-1, Forced draft fan FDF-DSA-41-500-1, Two-stage axial FD Fan, , Осевой, , FD FAN, ID FAN, Draft Equipment, FAN, Industrial fan.